CelciuXº - Multi-Loop temperature control - Control and Connectivity

CelciuXº is designed to handle complex temperature profiles thanks to Omron’s unique Gradient temperature Control (GTC) algorithm and to offer easy program-less communication with Omron and third-party PLCs and HMI. Above all, CelciuXº (EJ1) incorporates all “simple to use” clever temperature control technology, like 2-PID, disturbance control and various ways of tuning.

  • Interfaces to a wide range of industrial networks
  • Reduced engineering due to Programm-less communications, Smart Active Parts and Function Block Libraries
  • Available with screw terminals and screw-less clamp terminals
  • One unit handling various types of input, such as Pt, Thermocouple, mA, and V input
  • Gradient Temperature Control
Ekspertise

Applikationer

Præcis styring af 2D-temperaturprofiler

GTC (Gradient Temperature Control), Omrons unikke PID-styringsteknologi med loop-interaktion, sikrer, at en 2-dimensionel temperaturprofil forbliver konstant over et defineret område og dermed eliminerer skadelige effekter forårsaget hotspots på materialeflader som f.eks. metal, glas, plastic eller silikone-wafere. GTC gør det muligt at styre temperaturprofilens nøjagtige form i en hvilken som helst position.

Den perfekte løsning til styring af flere loops

Pålidelig, kompakt og kompromisløs styring betyder, at CelciuX° er det perfekte valg til grundlæggende styring af flere loops.

Maskinregulering med flere loops med HMI

Styring, overblik og datalogføring kunne ikke være bedre og nemmere end med CelciuX° kombineret med en direkte tilslutning til Omrons HMI’er.
Specifikationer & bestillingsinfo

Ordering information

Type

Control points

Control outputs

Auxiliary outputs

Other functions

Terminal

Order code

Basic unit

2

2 voltage (pulse)

2 transistor (NPN) 1

2 CT input 2 + 2 event input

M3 screws

EJ1N-TC2A-QNHB

Basic unit

2

2 voltage (pulse)

2 transistor (NPN) 1

2 CT input 2 + 2 event input

Screw-less clamp

EJ1N-TC2B-QNHB

Basic unit

2

2 current

2 transistor (NPN) 1

2 event input

M3 screws

EJ1N-TC2A-CNB

Basic unit

2

2 current

2 transistor (NPN) 1

2 event input

Screw-less clamp

EJ1N-TC2B-CNB

Basic unit

4

4 voltage (pulse)

-

-

M3 screws

EJ1N-TC4A-QQ

Basic unit

4

4 voltage (pulse)

-

-

Screw-less clamp

EJ1N-TC4B-QQ

High function unit

-

-

4 transistor (NPN)

4 event input

M3 screws

EJ1N-HFUA-NFLK

High function unit

-

-

4 transistor (NPN)

4 event input

Screw-less clamp

EJ1N-HFUB-NFLK

DeviceNet unit

-

-

-

-

Screw connector

EJ1N-HFUB-DRT

Ethernet unit3

-

-

-

-

3 x RJ45

EJ1N-HFU-ETN

End unit 4

-

-

2 transistor (NPN)

-

M3 screws

EJ1C-EDUA-NFLK

End unit 4

-

-

2 transistor (NPN)

-

Removable Connector

EJ1C-EDUC-NFLK

 

Type

Control points

Control outputs

Auxiliary outputs

Other functions

Terminal

Order code

Basic unit

2 (GTC)

2 voltage (pulse)5

2 transistor (NPN)

2 CT input6

M3 screws

EJ1G-TC2A-QNH

Basic unit

2 (GTC)

2 voltage (pulse)1

2 transistor (NPN)

2 CT input2

Screw-less clamp

EJ1G-TC2B-QNH

Basic unit

4 (GTC)

4 voltage (pulse)1

-

-

M3 screws

EJ1G-TC4A-QQ

Basic unit

4 (GTC)

4 voltage (pulse)1

-

-

Screw-less clamp

EJ1G-TC4B-QQ

High function unit

- (GTC)

-

4 transistor (NPN)

-

M3 screws

EJ1G-HFUA-NFLK

High function unit

- (GTC)

-

4 transistor (NPN)

-

Screw-less clamp

EJ1G-HFUB-NFLK

End unit7

-

-

2 transistor (NPN)

-

M3 screws

EJ1C-EDUA-NFLK

End unit3

-

-

2 transistor (NPN)

-

Removable Connector

EJ1C-EDUC-NFLK

Accessories

Current transformer

Diameter

Order code

5.8 dia.

E54-CT1

12.0 dia.

E54-CT3

Communications and cables

Description

Order code

G3ZA connecting cable 5 meter

EJ1C-CBLA050

USB programming cable

E58-CIFQ1

PC based configuration and tuning software CX-Thermo

EST2-2C-MV4

PROFIBUS Gateway

PRT1-SCU11

Specifications

Item

Type

EJ1_-TC2

EJ1_-TC4

Power supply voltage

24 VDC

Operating voltage range

85% to 110% of rated voltage

Power consumption

4 W max. (at maximum load)

5 W max. (at maximum load)

Input (see note)8

Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
ES1B Infrared Thermosensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C.
Analog input: 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V

Platinum resistance thermometer: Pt100, JPt100

Input impedance

Current input: 150Ω max., voltage input: 1 MΩ min.

Control outputs

Voltage output

Output voltage: 12 VDC ±15%, max. load current: 21 mA (PNP models with short-circuit protection circuit)

Transistor output

Max. operating voltage: 30 V, max. load current: 100 mA

-

Current output

Current output range: 4 to 20 mA or 0 to 20 mA DC
Load: 500 Ω max. (including transfer output)

(Resolution: Approx: 2,800 for 4 to 20 mA DC,
approx. 3,500 for 0 to 20 mA DC)

-

Event inputs

Input points

2

-

Contact input

ON: 1 kΩ max., OFF. 100 kΩ min.

-

Non-contact input

ON: Residual voltage: 1.5 V max.,
OFF: Leakage current: 0.1 mA max.

-

 

Outflow current: approx. 4 mA per point

-

Number of input and control points

Input points: 2, control points: 2

Input points: 4, control points: 4

Setting method

Via communications

Control method

ON/OFF control or 2-PID (with autotuning, selftuning, Heat & Cool autotuning and non-linear cool output selection)

Other functions

Two-point input shift, digital input filter, remote SP, SP ramp, manual manipulated variable, manipulated variable limiter, interference overshoot adjustment, loop burnout alarm, RUN/STOP, banks, I/O allocations, etc.

Alarm output

2 points via End unit

Communication

RS-485, PROFIBUS, Modbus, DeviceNet

RS-485, PROFIBUS, Modbus, DeviceNet

Size in mm (W×H×D)

31×96×109

Weight

180 g

Ambient temperature range

Operating -10°C to 55°C, Storage -25°C to 65°C (with no icing or condensation)

Ambient humidity range

Operating 25% to 85% (with no condensation)

Dimensions

Item

Size in mm (H×W×D)

EJ1N-HFU_-NFL_

95.4×31.0×104.9/109.0

EJ1N-HFUB-DRT

90.9×31.0×82.2

EJ1C-EDU

95.4×15.7×76.2/79.7


1. For heating/cooling control applications, the auxiliary outputs on the 2-point models are used for cooling control.
On the 4-point models, heating/cooling control can be performed for two input points only.

2. When using the heater burnout alarm, purchase a Current Transformer (E54-CT1 or E54-CT3) separately.

3. This unit mounts to the left of the CelciuX° (EJ1) configuration and enables PROFINET or Modbus/TCP network connection. Combine the HFU-ETN with an EDU_-NFLK end unit to use with other devices supporting Modbus-RTU like E5_N temperature controllers and MX2 Inverters.

4. An End unit is always required for connection to a Basic unit or an HFU. An HFU cannot operate without a Basic unit.

5. Heating/cooling control is not supported for gradient temperature control.

6. When using the heater burnout alarm, use a Current Transformer (E54-CT1 or E54-CT3) (sold separately).

7. An End-unit (EDU) is always required to connect an HFU and or a Basic TC unit for Communications and Power supply.
A GTC (Gradient Temperature Control) basic TC unit always requires a GTC HFU unit.

8. Inputs are fully multi-input. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be selected.

1. For heating/cooling control applications, the auxiliary outputs on the 2-point models are used for cooling control.
On the 4-point models, heating/cooling control can be performed for two input points only.

2. When using the heater burnout alarm, purchase a Current Transformer (E54-CT1 or E54-CT3) separately.

3. This unit mounts to the left of the CelciuX° (EJ1) configuration and enables PROFINET or Modbus/TCP network connection. Combine the HFU-ETN with an EDU_-NFLK end unit to use with other devices supporting Modbus-RTU like E5_N temperature controllers and MX2 Inverters.

4. An End unit is always required for connection to a Basic unit or an HFU. An HFU cannot operate without a Basic unit.

5. Heating/cooling control is not supported for gradient temperature control.

6. When using the heater burnout alarm, use a Current Transformer (E54-CT1 or E54-CT3) (sold separately).

7. An End-unit (EDU) is always required to connect an HFU and or a Basic TC unit for Communications and Power supply.
A GTC (Gradient Temperature Control) basic TC unit always requires a GTC HFU unit.

8. Inputs are fully multi-input. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be selected.

Hjælpeudstyr

EJ1N-HFU-ETN

EJN-HFU-02.jpg
EJ1N-HFU-ETN giver mulighed for at tilslutte en CelciuX° (EJ1) multiloop PID-controller i panelet til PROFINET og Modbus/TCP.

PRT1-SCU11

PRT1_SCU11
Denne gateway understøtter alle produkter, der er udstyret med CompoWay/F, herunder temperaturregulatorer, digitale panelmetre osv.
Software

CX-Thermo

CX-Thermo_no_version .jpg
CX-Thermo muliggør hurtigere parameter set-up, let enheds justering og enklere vedligeholdelse. CX-Thermo reducerer markant den tid og indsats der er nødvendig for at indstille og styre temperaturregulatorer. CX-Thermo giver avancerede oprettelses-, redigerings- og batchdownloads funktioner.

CX-One

CX-One_Screen
CX-One-software gør brugerne i stand til at opbygge, konfigurere og programmere en række forskellige enheder som f.eks. PLC'er, HMI'er og motion control-systemer og netværk ved hjælp af en enkelt softwarepakke med én installation og ét licensnummer. Det gør det muligt at konfigurerer, programmere og servicerer Omron's automatiseringssystemer med minimal træning.

CX-Supervisor

CX-Supervisor_splash.jpg
CX-Supervisor handler om design og betjening af pc-visualisering og maskinstyring. Den er ikke blot nem at bruge til små overvågnings- eller styringsopgaver, men er også virkeligt effektiv, når det handler om at designe de mest sofistikerede applikationer.
Downloads

Brochurer

Vis alle brochurer

Datablade

Vis alle datablade

Manualer

Vis alle manualer

Har du et spørgsmål?

Vi er klar til at hjælpe.

Kontakt os

Abonnér på produktopdateringer

Nyhedsbreve om produktinnovationer, løsninger og serviceydelser direkte i din indbakke.

Tak for din tilmelding til Omrons nyhedsbrev. Du vil i løbet af kort tid modtage en e-mail fra os, som indeholder et link hvormed du aktiverer din tilmelding til nyhedsbrevet. Denne metode anvendes i henhold til lovgivningen for at sikre, at ingen kan misbruge din e-mail addresse.

Vi har desværre tekniske problemer. Din formular er ikke modtaget. Vi undskylder og beder dig om at prøve igen senere. Detaljer: [details]

Download

Produktdokumentation

Download datablade, manualer og brochurer.

Gennemse downloadcenter

Kurser

Bliv uddannet af vores bedste ingeniører. Fra begynder til udvidet niveau.

Se tilgængelige kurser