K8DS-PA

Funktioner

3-faset spændingsasymmetri, fasefølge, fasebrud

K8DS-PA overvåger spændingsasymmetri, fasefølge og fasebrud for 3-fasede strømforsyninger med 3 ledere.

  • Verdensomspændende effektspecifikationer understøttes af én enhed
  • Fasefølge, fasebrud: Reaktionstid for drift maks. 0,1 sek.
  • Asymmetri: Tidsindstilling for drift fra 0,1 til 30 sek.
  • Nulstillingsmetode: Automatisk
  • LED-indikatorer: Strøm (grøn), relæudgang (gul), alarmudgang (rød)
  • Robust driftstemperatur: -20 til 60 ⁰C
  • 17,5 mm (w) element
  • Større modstand mod frekvensomformerstøj
  • Verdensomspændende effektspecifikationer understøttes af én enhed
Specifikationer & bestillingsinfo

Ordering information

Rated input

Order code

3-phase 3-wire mode

200, 220, 230, 240 VAC

K8DS-PA1

3-phase 3-wire mode

380, 400, 415, 480 VAC

K8DS-PA2

Specifications

Ambient operating temperature

-20 to 60°C (with no condensation or icing)

Storage temperature

-25 to 65°C (with no condensation or icing)

Altitude

2,000 m max.

Input frequency

50/60 Hz (AC power supply)

Output relays
(1 × SPDT, normally closed operation)

Resistive load

5 A at 250 VAC or at 30 VDC

Maximum contact voltage

250 VAC or 30 VDC

Maximum contact current

5 A

Maximum switching capacity

1,250 VA, 150 W

Mechanical life

10,000,000 operations

Electrical life

50,000 operations at 5 A, 250 VAC or 30 VDC

Degree of protection

Terminal section: IP20

Case material

PC UL94 V-0

Weight

Approx. 65 g

Rated input voltage

K8DS-PA1

3-phase, 3-wire mode: 200, 220, 230, 240 VAC

K8DS-PA2

3-phase, 3-wire mode: 380, 400, 415, 480 VAC

Asymmetry operation (ASY.)

Operating value setting range

Asymmetry rate: 2% to 22%

Operating value

100% operation at set value

Asymmetry operating value = rated input voltage x asymmetry set value [%]

The asymmetry operation will function when the difference between the highest and lowest voltage phases equals or exceeds the asymmetry operating value

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating time (T)

Asymmetry

0.1 to 30 s

Phase-sequence

0.1 s ±0.5 s

Phase-loss

0.1 s max.

Power ON lock (LOCK)

1 s ±0.5 s

Overload capacity

Continuous input: 500 V

Repeat accuracy

Operating value

±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, 50/60 Hz sine wave input)

Operating time

±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Indicators

Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red

Applicable standards

Conforming standards

EN 60947-5-1
Installation environment (pollution level 2, installation category III)

EMC

EN 60947-5-1

Safety standards

UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No. 14, CCC: GB14048.5

Size (H × W × D)

80 × 17.5 × 74 mm

Har du et spørgsmål?

Vi er klar til at hjælpe.

Kontakt os

Abonnér på produktopdateringer

Nyhedsbreve om produktinnovationer, løsninger og serviceydelser direkte i din indbakke.

Tak for din tilmelding til Omrons nyhedsbrev. Du vil i løbet af kort tid modtage en e-mail fra os, som indeholder et link hvormed du aktiverer din tilmelding til nyhedsbrevet. Denne metode anvendes i henhold til lovgivningen for at sikre, at ingen kan misbruge din e-mail addresse.

Vi har desværre tekniske problemer. Din formular er ikke modtaget. Vi undskylder og beder dig om at prøve igen senere. Detaljer: [details]

Download

Produktdokumentation

Download datablade, manualer og brochurer.

Gennemse downloadcenter

Kurser

Bliv uddannet af vores bedste ingeniører. Fra begynder til udvidet niveau.

Se tilgængelige kurser