F3S-TGR-N_X

Funktioner

Kontaktfrie afbrydere af Reed-typen til eksplosionsfarlige områder

Eksplosionssikre kontakfrie afbrydere af Reed-typen overvåger status for sikkerhedsdøre inden for petrokemiske og fødevaretekniske anvendelsesområder med eksplosive atmosfærer.

  • Baseret på Reed-teknologi
  • Tilslut op til 6 kontakter i serieforbindelse
  • Kompatibel med alle Omrons sikkerhedscontrollere
  • Tilpasset arbejde bag rustfrit stål
  • Ingen kontakt – ingen slitage – ingen partikler
  • Kompensation for mekaniske tolerancer
  • Velegnet til højtryksrensning, CIP/SIP-processer takket være IP69K (formonteret kabel)
  • Overholder sikkerhedskategorier op til PLe iht. EN ISO13849-1
Specifikationer & bestillingsinfo

Ordering information

Elongated sensors

Type

Cable connection

Contact configuration

Order code

 

5 m pre-wired

2NC/1NO

F3S-TGR-NLMX-21-05

10 m pre-wired

2NC/1NO

F3S-TGR-NLMX-21-10

Barrel sensors

Type

Cable connection

Contact configuration

Order code

 

5 m pre-wired

2NC/1NO

F3S-TGR-NBMX-21-05

10 m pre-wired

2NC/1NO

F3S-TGR-NBMX-21-10

Specifications

Mechanical data

 

Elongated sensors

Barrel sensors

Serial switching

up to 6 pcs.

Indicator

-

None

Operating distance

OFF  ON (Sao)

10 mm close

ON  OFF (Sar)

22 mm open

Actuator approach speed

Min.

Max.

4 mm/s

1000 mm/s

Operating temperature

-

-20°C to +60°C

Enclosure protection

Flying lead

IP 67 Certification for IP67 but can be used for SIP/CIP and high pressure cleaning like IP69K)

Material

-

Stainless steel 316

Electrical data

 

Elongated sensors

Barrel sensors

Sensor technology

-

Reed

Power supply

-

24 VDC±15%

Switching current

Min.

1 mA, 10 VDC

Rated loads

NC contacts

NO contact

Max.

0.6 A, 230 VAC/24 VDC (internally fused)

0.2 A, 230 VAC/24 VDC

Ex specification

 

II 2G Ex mb IIC T6Gb, II 2D Ex mb IIC T80 Db IP67*
(*Product is fully encapsulated which is considered to provide Ingress Protection to at least IP67)

Zones 1 and 2 (Gas), Zones 21 and 22 (Dust)

(An area where Gas and Dust is likely to occur in use)

IEC/EN 60079-0, IEC/EN 60079-18

Approved standards

EN standards certified by TÜV Rheinland

EN ISO 13849-1

EN 60204-1

EN 62061

EN ISO 14119

EN/IEC 60947-5-3

UL 508, CSA C22.2

BS 5304

EN 1088-1

Accessories

 

Order code

Actuators

for F3S-TGR-NLMX

F39-TGR-NLMX-A

for F3S-TGR-NBMX

F39-TGR-NBMX-A

Mounting screws

Set of Torx safety screws
(M4, 4 × 30 mm, 4 × 20 mm, 4 × 10 mm; incl. washers and Torx bit)

F39-TGR-N-Screws

Spacer (8 mm, Set of 2pcs.)1

for F3S-TGR-NLMX

F39-TGR-NLR-SPACER

Wiring examples (Single head connection)

G9SA

Single sensor application with G9SA-301
(up to PLe acc. EN ISO 13849-1)

 


1. Spacers are needed to prevent influences if switch is mounted on ferromagnetic background (e. g. reduced switching distance, EMC influences)

1. Spacers are needed to prevent influences if switch is mounted on ferromagnetic background (e. g. reduced switching distance, EMC influences)

Har du et spørgsmål?

Vi er klar til at hjælpe.

Kontakt os

Abonnér på produktopdateringer

Nyhedsbreve om produktinnovationer, løsninger og serviceydelser direkte i din indbakke.

Tak for din tilmelding til Omrons nyhedsbrev. Du vil i løbet af kort tid modtage en e-mail fra os, som indeholder et link hvormed du aktiverer din tilmelding til nyhedsbrevet. Denne metode anvendes i henhold til lovgivningen for at sikre, at ingen kan misbruge din e-mail addresse.

Vi har desværre tekniske problemer. Din formular er ikke modtaget. Vi undskylder og beder dig om at prøve igen senere. Detaljer: [details]

Download

Produktdokumentation

Download datablade, manualer og brochurer.

Gennemse downloadcenter

Kurser

Bliv uddannet af vores bedste ingeniører. Fra begynder til udvidet niveau.

Se tilgængelige kurser